Grundfos S2.100.300.300.4.62E.C.253 Cast Iron 30 kW Sewage Pump for Wastewater Transfer with 2-Channel Impeller
SKU: 96810451

Grundfos S2.100.300.300.4.62E.C.253 Cast Iron 30 kW Sewage Pump for Wastewater Transfer with 2-Channel Impeller

$44,488.24 GST Included
FREE shipping on orders over $100 Australia-wide*
Fast Dispatch
Australia-Wide
Expert Advice
(08) 9240 2992
Genuine
Official Grundfos
24 Months
Peace of Mind
Max Flow
20100 L/Min
Max Head
10.4 m
Power
30 kW / 415v
Ideal Use
Flooded Wastewater Channels

Product Overview

With flow capacity reaching 20100 L/min and maximum head of 10.4 m, the Grundfos S2.100.300.300.4.62E.C.253.G.N.D.513GPA submersible sewage pump is suited to wastewater, process water and unscreened raw sewage transfer where very high flow rates at low heads are required. The Variant C cooling jacket enables continuous submerged operation at depths up to 20 m.

A 30 kW motor (P2) at 1482 rpm from a 415 V three-phase supply draws 64 A with 89% efficiency at full load and 87% at 3/4 load. The 253 mm impeller delivers the specified performance, with DN300 outlet and DN100 inlet connections carrying a PN10 pressure rating for this configuration.

Hydraulic performance is provided by a 2-channel cast iron impeller with 100 mm free passage, with the impeller diameter and dual-channel configuration matched to the E lifting height class requirements. The impeller geometry determines the head and flow characteristics for this Range 62 model.

Cast iron construction with IP68 enclosure and Class F insulation provides submerged durability, with primary silicon carbide and secondary silicon carbide-carbon shaft seals preventing liquid ingress. Integrated moisture sensors are fitted as standard, and the 15 m H07RN-F AT cable supports Star/Delta starting.

FEATURES

  • Range 62 Motor Design: The motor frame incorporates standardized external and internal dimensions, cooling system configuration, shaft seal arrangement and bearing specification common to all pumps in the Range 62 series.
  • 2-Channel Cast Iron Impeller: The dual-channel impeller design provides stable hydraulic performance across the operating range while maintaining efficient solids handling capability for municipal wastewater applications.
  • 100 mm Free Passage: The internal clearance through the impeller and volute allows solids and unscreened sewage particulates to pass without blocking the hydraulic flow path during operation.
  • DN300 / DN100 Connection: The outlet connection is sized at DN300 with a PN10 pressure rating, while the inlet connection is DN100, matching the hydraulic design requirements of this configuration.
  • Variant C Cooling Jacket: The integrated cooling jacket surrounds the motor stator to dissipate heat during continuous submerged operation, maintaining stable motor temperatures in wet well installations.
  • IP68 Enclosure Protection: The motor housing is fully sealed against permanent submersion, with the IP68 rating confirming suitability for continuous operation at depths up to 20 m.
  • Silicon Carbide Shaft Seals: The primary shaft seal uses silicon carbide faces while the secondary seal employs a silicon carbide-carbon combination, providing two-stage protection against liquid ingress into the motor compartment.
  • Integrated Moisture Sensors: Sensors are fitted within the motor housing to detect the presence of moisture, providing early indication of potential seal degradation or liquid ingress during service.

IMPORTANT: Bulk freight charges apply. Please contact us for a freight quote before ordering.

SPECIFICATIONS
Max Flow20100 L/Min
Max Head10.4 m
Power30 kW / 415v
Rated Current64 Amps
Suitable ForFlooded Wastewater Channels
Body MaterialCast iron
Liquid Temperature0°C to +40°C
Inlet Size300 mm
Outlet Size300 mm
Warranty24 Months
Documents
Product Brochure Download
Specification Datasheet Download
Operating Manual Download
Data Booklet Download
Service Instructions Download

Suburban sewage districts facing moderate static lift utilize the Grundfos S2.100.300.300.4.62E.C.253 to convey treated effluent between regional processing basins. The dual-vane impeller balances hydraulic loads, prolonging bearing life and eliminating mechanical vibration.

  • Suburban Networks
  • Effluent Basins
  • Transfer Pits
  • Treatment Facilities

Warranty & Returns

All products supplied by Foundation Pumps are covered by a minimum 12-month warranty unless otherwise stated. Some brands may offer longer manufacturer warranties. Warranty covers manufacturing defects, faulty materials and workmanship under normal use.

  • Products must be installed correctly and in accordance with the manufacturer’s instructions.
  • Warranty does not cover incorrect installation, misuse, dry running, normal wear and tear, unauthorised repairs or damage caused by external factors.
  • Proof of purchase, photos, videos and installation details may be requested when assessing a warranty claim.
  • The customer is responsible for returning the product to Foundation Pumps or the nominated service centre unless otherwise agreed.
  • Removal, reinstallation, labour and associated site costs are generally the customer’s responsibility unless required under Australian Consumer Law.
  • Change-of-mind returns may be accepted within 30 days provided the product is unused, uninstalled and returned in its original packaging.
  • Customers are responsible for return freight costs for change-of-mind returns.
  • Restocking fees may apply to special-order, bulky or non-stocked products.
  • Used, installed or specially ordered products may not be eligible for change-of-mind returns.
  • If a product arrives damaged or faulty, please contact Foundation Pumps as soon as possible so we can assist with the appropriate repair, replacement or refund.

Your rights under Australian Consumer Law are not affected.

Product Brochure
Download
Specification Datasheet
Download
Operating Manual
Download
Data Booklet
Download
Service Instructions
Download
What maximum submergence depth and operating liquid temperature range govern this unit?

Submerged wastewater service allows the S2.100.300.300.4.62E.C.253 to be positioned at installation depths up to approximately 20 m with temperatures up to 40°C.

Overcoming vertical elevation rise, what dynamic lift head applies to this municipal pump?

Lifting wastewater from deep collection basins, the Grundfos S2.100.300.300.4.62E.C.253 attains a peak dynamic head of approximately 10.4 m.

How many liters of raw sewage per minute can this pump discharge across its connection?

High-volume fluid transfer peaks at a delivery flow rate of approximately 20100 L/Min on the S2-100-300-300-4-62E-C-253, plumbed with a DN 300 (standard flanged connection).

Which spherical solids passage capability and alloy construction are incorporated into this unit?

Fluid containment and passage on the S2 100 300 300 4 62E C 253 are secured by Cast iron housing and wetted components and an optimized channel impeller supporting spherical debris up to 100 mm.

What motor power in kilowatts and electrical supply voltage feed run this heavy municipal pump?

Power requirements for the S2.100.300.300.4.62E.C.253.G.N.D.513GPA demand 415 V, 50 Hz, three-phase to drive an electric motor rated at 30 kW with an operating current of 64 A.

Need help choosing the right pump?

Our team of pump experts are here to help you find the perfect solution for your application.

  • Free expert advice
  • Pump sizing & system recommendations
  • Fast response — call or email us

Recently viewed