You may also like
Single-phase dual-pump installations requiring run capacitors can be configured with the RCAP option. This single-phase 230Vac panel features run capacitors while managing dual-pump duty alternation and motor protection.
The controller regulates dual-pump operation with automatic duty alternation on start and after 30 minutes of continuous run, or after 6 hours in recirculation mode. The standby pump engages when the standby start input closes, supported by a 3-second staggered start delay to prevent simultaneous starting surges. Independent electronic current sensing protects each motor across selectable 0.1–6A and 5–16A overload ranges.
Operator feedback is provided via a dual-pump capacitive touch keypad displaying power, system enable, level alarms, pump run states, auto/manual modes, and fault diagnostics. Built-in strobe and audible buzzer alarms feature smart chirp silencing. DIP switches allow configuration for Level Control (up to 5 floats) or Pressure Control (up to 3 pressure switches).
The unit is housed in a 400 x 400 x 200 mm powder-coated mild steel enclosure with an inner door, providing an IP56 rating for outdoor mounting. Features include a padlockable mains isolator, individual pump circuit breakers, a removable gland plate, a volt-free BMS common fault relay, and Modbus RTU Serial RS485 connections for SCADA.
Features
- Powder-coated mild steel enclosure measuring 400 mm high by 400 mm wide by 200 mm deep with removable gland plate
- IP56 rated with inner door, for outdoor mounting
- Run capacitors option (RCAPN) for single-phase pump operation
- Single-phase 230Vac supply voltage operating two pumps with 240Vac switched outputs
- Automatic duty alternation on start and runtime, standby pump assist, and fault alternation
- 3-second staggered start delay preventing simultaneous electrical inrush current draw
- Independent electronic overload protection per pump with selectable 0.1–6A and 5–16A ranges
- Dual-pump capacitive touch keypad with status LEDs, mute/reset, and mode selection buttons
- Padlockable mains isolator, individual circuit breakers, volt-free BMS fault output, and RS-485 port
Recently viewed