You may also like
Three-phase dual-pump installations can incorporate a battery backup high level alarm configuration. Designed for a 400Vac three-phase supply (4 core and earth with neutral), this panel features the BBHLS battery backup high level alarm option alongside three-phase contactor control and motor current sensing.
The unit operates two three-phase pump contactors with automatic duty alternation on start and after 30 minutes of continuous running, or after 6 hours in recirculation mode. The standby pump starts when the standby start input closes, supported by a 3-second staggered start delay. Current transformers monitor two phases per pump, providing electronic overload protection across selectable 0.1–6A and 5–16A ranges.
The panel features a dual-pump capacitive touch keypad with indicator lights for power, system enable, level alarms, pump running states, auto/manual modes, and fault diagnostics. Local alarms include an integrated visual strobe and an audible buzzer with smart chirp silencing. DIP switches allow configuration for Level Control (up to 5 floats) or Pressure Control (up to 3 pressure switches).
Built into a 400 x 400 x 200 mm powder-coated mild steel enclosure with an inner door, the panel is IP56 rated for outdoor mounting. Features include a padlockable mains isolator switch, individual pump circuit breakers, contactors, a removable gland plate, a volt-free BMS common fault relay, and Modbus RTU Serial RS485 connections for SCADA.
Features
- Powder-coated mild steel enclosure measuring 400 mm high by 400 mm wide by 200 mm deep with removable gland plate
- IP56 rated with inner door, for outdoor mounting
- Integrated battery backup high level alarm (BBHLS)
- Three-phase 400Vac supply (4 core and earth with neutral) operating two pumps via contactors
- Two current transformers per pump monitoring two phases with selectable 0.1–6A and 5–16A overload ranges
- Automatic duty alternation on start and runtime, standby assist, and 3-second staggered start delay
- Dual-pump capacitive touch keypad with multi-state LED indicators and touch buttons
- Padlockable mains isolator switch and dedicated circuit breaker protection per pump
- Volt-free BMS common fault relay output and Modbus RTU Serial RS485 connections for SCADA
Recently viewed