Skip to Product Info
    • MATelec HydroWHIZ FPC-63441-(AA-D)/BMS Mild Steel IP56 Inner Door 1PH 1.6-13A DOL Four Pump Controller
    • MATelec HydroWHIZ FPC-63441-(AA-D)/BMS Mild Steel IP56 Inner Door 1PH 1.6-13A DOL Four Pump Controller
    • MATelec HydroWHIZ FPC-63441-(AA-D)/BMS Mild Steel IP56 Inner Door 1PH 1.6-13A DOL Four Pump Controller

    MATelec HydroWHIZ FPC-63441-(AA-D)/BMS Mild Steel IP56 Inner Door 1PH 1.6-13A DOL Four Pump Controller

    Vendor: Matelec Type: Controllers
    SKU: FPC-63441-AA/BMS
    Regular Price $4,643.07 AUD
    Including GST Shipping calculated at checkout.
    Overload Rating: FPC-63441-AA/BMS (1.6-2.5 Amp)
    Payment & Security

    Your payment is processed securely.

    • American Express
    • Apple Pay
    • Google Pay
    • Mastercard
    • Shop Pay
    • Union Pay
    • Visa
    Pairs well with

    The four-pump MATelec FPC-63441-(AA-D)/BMS operates from 230Vac and adds BMS volt-free outputs to the standard HydroWHIZ multi-pump control functions. The enclosure layout includes a protective inner door for touch safety, a removable gland plate to simplify cable entry, and a pad-lockable mains power isolator switch. Load sharing logic alternates the active duty pump upon system start or after continuous runs, helping equalise pump run hours.

    The panel connects to a 230Vac power supply, distributing switching power to the connected pump motor terminal connections. Motor winding protection is provided by thermal overloads adjustable within the 1.6-13A range, protecting the pump motor against overload. Field switch lines and logic circuits operate at 24Vdc to isolate remote sensors, backed by circuit-breaker protection on the control lines.

    Flexible setup options include level empty and fill, pressure boosting, or temperature control. System states are governed by a 4-20mA analogue transducer signal and up to eight digital inputs representing start, standby, and alarm conditions. To minimize water surge and line current draw, pumps are staged sequentially with a 3-second staggered start delay and a 1-second staggered stop delay.

    Live operating diagnostics are accessible on the colour touchscreen HMI, which plots analogue trends and logs pump start and run hours. Local alarms activate an onboard visual strobe and a mutable audible buzzer, with audible buzzer mute function. BMS hardware features include dedicated volt-free relay outputs for power on, high level, pump run, and individual pump faults. Mechanical protection is provided by high and low level protection, feedback signal fault protection, cycle protection, and a 7-day pump anti-seize routine.

    Features

    • Audible siren output terminal on the control board for integration of remote strobe and buzzer indicators.
    • Microprocessor-controlled board memory that allows full factory parameter reset via HMI menus.
    • Removable inner door configuration that isolates high-voltage terminal wiring from HMI controls.
    • Circuit-breaker protected low-voltage control circuitry operating on a dedicated 24Vdc supply loop.
    • Dedicated volt-free relay terminal for high level alarm reporting to central building management systems.
    • Individual pump run volt-free contacts to track separate operating statuses on remote panels.
    • Separate pump fault volt-free relay terminals to isolate and report specific pump failures to the BMS.